Metacaulk Composite Sheet
Rigid fire-resistive panel with reinforced intumescent material bonded to non-magnetic #304 stainless steel sheet. For restoring fire integrity of large openings. Up to 4-hour fire resistance. Expansion ratio 1:25. Lightweight, cut with common tools.

🛡️
UL-Classified SystemsComponents of tested UL firestop systems
✔️
Authorized DistributorGenuine Metacaulk® / RectorSeal
📄
TDS & SDSFull technical documentation
🚚
Same-Day ShippingOrder by 11 AM CST
📞
Spec & Submittal SupportCode & system help
Key features
- UL Classified systems up to 4 hours
- 36" x 36" sheets, cut with standard tools
- Non-magnetic stainless steel backing
- Re-enterable, VOC compliant
- Expansion ratio 1:25
Typical applications
- Blank openings
- metallic pipes
- cable trays
- combustible pipes (cPVC
- PVC
- RNC)
Technical data
| VOC | <10 g/L |
|---|---|
| Color | Silver |
| Weight | 4.8 lb (2.17 kg) |
| Chemical Base | Graphite based on Synthetic compound (encapsulated) |
| Sheet Size | 36" x 36" |
| Thickness | 0.15 ± 0.05" |
| Expansion Ratio | 1:25 |
| Expansion Pressure | 1.391 N/mm² (13.91 Bar) |
Installation overview
- Clean all joints, openings, and penetrating items
- Cut sheet to overlap opening by min 2 in. on all sides
- Contour around penetrating items, max 3/8 in. gap
- Apply Joint Strip or FR Putty under sheet around perimeter
- Secure with 3/8" x 1-1/4" steel fasteners at 6" centers, steel side exposed
- Apply 1/2" bead of Metacaulk Putty or 1000 at penetrant interface